Synchronous Generator
An alternating current machine in which the frequency of the generated voltages and the speed of the machine are in a constant ratio. IEC 60050.
Synchronous Generator in PSP-UFU
Synchronous generators are the power source for load flow and stability calculations, and they are also one of the main contributors to fault currents.
Only buses that have this element connected can be considered reference buses. PV buses must contain either a synchronous generator or a synchronous motor (synchronous condenser).
The data form is divided into two sections: the first for general, load flow, and fault data, and the second for stability data. The latter also allows access to synchronous machine controls handled by the control editor.
The data regarding the positive sequence impedances of the synchronous generator entered in the “Fault” tab are used both for short-circuit studies and for harmonic studies.
These data are ignored in load flow studies (not used in this study) and in stability studies (data entered in a specific stability form are used).
Synchronous Generator in load flow
The synchronous generator is the power source in PSP-UFU’s load flow study. Its behavior differs depending on the type of bus connected:
- Reference bus: The entered active and reactive power data are ignored, as this element will be used to complete the power balance in the load flow study;
- PV bus: The active power data is considered, but the reactive power data is ignored. The reactive power value is used to keep the voltage magnitude constant at the connected bus;
- PQ bus: For generators connected to this bus, both the entered active and reactive power values are considered.
Synchronous Generator in short-circuit study
While generators in the load flow study are modeled only by currents injected into the buses, for short-circuit analysis a voltage behind an impedance is used. The figure below shows the current path and equivalent circuit of each sequence in the generators.
The generated voltages are only positive sequence, since the generator always supplies balanced three-phase voltages. Therefore, the positive sequence network consists of a pre-fault voltage behind a positive sequence impedance. The negative and zero sequence networks contain no electromotive forces but include the generator’s negative and zero sequence impedances.
The current flowing through the impedance between neutral and ground is . From figure (c) above, it can be seen that the zero sequence voltage drop from point a to ground () is:
The zero sequence network, which is a single-phase circuit assumed to carry only zero sequence current, must therefore have an impedance defined by the following equation:
If the generator is not grounded, no zero sequence current will flow through it. In this case, depending on the transformer connection near the ungrounded generator, the following error message may be displayed:
This happens because the zero sequence admittance matrix is singular. To work around this issue, choose one of the two solutions below:
- Check the "Neutral grounded" option and enter a high grounding reactance value (, for example);
- Or, at the generator bus, insert a reactor with a low reactive power value (, for example).