Skip to main content

Transformer

A static device with two or more windings that, by electromagnetic induction, transforms a system of alternating voltage and current into another system of voltage and current generally of different values and at the same frequency, with the purpose of transmitting electrical energy. free translation - IEC 60050.

Transformer in PSP-UFU

Transformers with any connections and phase shifts between primary and secondary voltages can be inserted in PSP-UFU. For this, transformers must be modeled representing their tap (tt) and phase shift (ϕ\phi), using an ideal transformer with transformation ratio t:1\overline{t}:1 in series with its impedance (yT=rT+jxT\overline{y}_T = r_T + jx_T), where t\overline{t} is a complex number (tϕt\angle\phi).

Caution

The model used in PSP-UFU does not consider the magnetizing branch or mutual impedances between phases.

The figure below shows the transformer model implemented in PSP-UFU:

PI Model of the line

Where:

  • rT\bold{r_T} is the total transformer resistance;
  • xT\bold{x_T} is the total inductive reactance of the transformer;
  • t\bold{\overline{t}} is the complex tap of the transformer.

The relationship between the voltages and currents of generic buses ii and jj is given by the matrix equation:

[I˙ijI˙ji]=[yTt2yTtyTtyT]×[V˙iV˙j]\begin{bmatrix} \dot{I}_{ij}\\ \dot{I}_{ji} \end{bmatrix} = \begin{bmatrix} \displaystyle \frac{\overline{y}_T}{t^2} & -\displaystyle \frac{\overline{y}_T}{\overline{t}^*}\\ -\displaystyle \frac{\overline{y}_T}{\overline{t}} & \overline{y}_T \end{bmatrix} \times \begin{bmatrix} \dot{V}_{i}\\ \dot{V}_{j} \end{bmatrix}

As in lines, the two-winding transformer must be inserted between buses, but the nominal voltages of these buses do not need to be identical.

Caution!

The first selected bus will be the primary side, which is indicated by a circle. To change the primary side after insertion, simply disconnect the transformer nodes and reconnect them switching the buses, using the CAD tools.

Transformers in short-circuit studies

Just as in load flow studies, the representation of system elements for short-circuit studies is done through equivalent circuits inserted into the bus admittance matrix. In unbalanced faults it is necessary to form three sequence admittance matrices: positive, negative, and zero.

The positive sequence admittance matrix is built the same way as in load flow studies. In the negative sequence, the phase shift angle between primary and secondary voltages (ϕ\phi) must be inverted, since negative sequence phasors are displaced in the opposite direction. Thus, the matrix representing the admittances in the previous equation must be replaced by the following expression:

[YiiYijYjiYjj]=[yTt2yTtyTtyT]\begin{bmatrix} \overline{Y}_{ii} & \overline{Y}_{ij}\\ \overline{Y}_{ji} & \overline{Y}_{jj} \end{bmatrix} = \begin{bmatrix} \displaystyle \frac{\overline{y}_T}{t^2} & -\displaystyle \frac{\overline{y}_T}{\overline{t}}\\ -\displaystyle \frac{\overline{y}_T}{\overline{t}^*} & \overline{y}_T \end{bmatrix}

The negative sequence impedance in transformers must be treated specifically due to different types of connections. The figure below shows the equivalent circuits for each type of two-winding transformer connection. The arrows indicate possible paths for zero-sequence current flow.

Zero sequence equivalent circuits of transformers

For transformers with grounded wye connection, if the neutral-to-ground connection has an impedance zn\overline{z}_n, the zero sequence equivalent circuit must have an impedance of 3zn3\overline{z}_n in series with the equivalent resistance and reactance of the transformer.

Transformer Data Editing Form

The image below shows the data insertion/modification form for transformers:

Transformer form in PSP-UFU

This form is subdivided into two distinct contexts:

  • General: where general transformer information, load flow data, its connection, and phase shift are entered;
  • Fault: where zero sequence impedances and grounding impedances are entered.

Besides these two contexts, the "Stability" button can be seen in the lower left of the form. This form, common to several other elements, allows insertion and/or removal of the transformer during the stability study.

Transformer switching form

Name

Identification of the electrical element. Any number of characters can be entered in Unicode standard.

All power components in PSP-UFU have this field.

Nominal voltage

Non-editable field showing the primary and secondary voltage of the transformer. To change this field, the corresponding field in the connected bus must be edited.

Base voltage

Voltage used to convert the entered impedance parameters from Ω\Omega to p.u.p.u. The voltages selected by a dropdown box are edited in the connected bus forms.

Information

Base voltage is ignored if the data entered is already in p.u.p.u.

Rated power

Transformer rated power, entered in MVA, kVA, or VA.

This field is especially important if the option "Use rated power as base" is selected.

Transformer impedance

Transformer series impedance (resistance and inductive reactance), entered in p.u.p.u. or Ω\Omega. If impedances are entered in Ω\Omega, the selected base voltage will be used for conversion to p.u.p.u.

Connection

Transformer connection used for zero sequence current calculation in unbalanced faults involving ground (phase-ground and phase-phase-ground).

The following connections are available:

  1. YgroundedYgroundedY_{grounded}-Y_{grounded}
  2. YYgroundedY-Y_{grounded}
  3. YgroundedYY_{grounded}-Y
  4. YYY-Y
  5. ΔYgrounded\Delta-Y_{grounded}
  6. ΔY\Delta-Y
  7. YgroundedΔY_{grounded}-\Delta
  8. YΔY-\Delta
  9. ΔΔ\Delta-\Delta

TAP

Transformer tap relative to the primary.

Caution!

The tap in PSP-UFU must be entered as the ratio between the nominal primary voltage and the tap voltage (TAP=VnominalVtap)\left(\text{TAP} = \frac{V_{nominal}}{V_{tap}}\right).

Phase shift

Transformer phase shift relative to the primary, in degrees. This value is independent of the connection type, so for connections other than YYY-Y (grounded or not) and ΔΔ\Delta-\Delta, the correct phase angle must be entered.

Use rated power as base

If this option is selected, the program will use the transformer's rated power as the base for unit conversion; otherwise, the system base power will be used.